LIGHTING
Power, Control & Instrument Cable
Nexans
Kukdong - IEC Offshore Cable
Instrument circuit up to 250V, instrument safe systems. Fixed installation for instrument, communication, control and alarm systems in both explosion risk and safe areas, emergency and critical systems. Maximum operating conductor temperature 90°C
Construction Details
- Conductor : Circular tinned stranded copper as per IEC 60228, Class 2
- Insulation : Mica tape & Halogen Free Ethylene Propylene Rubber
- Pair twisting : Two insulated cores twisted together with suitable lay length
- Cabling (with filler)
- Collective screening : Wrapped by copper or aluminium backed polyester tape with tinned copper drain wire
- Inner covering : Halogen free compound
- Armour : Tinned copper wire braid as per IEC 60092-376
- BFCU (option) : Galvanized steel wire braid as per IEC 60092-376
- Outer sheath : Halogen free thermosetting compound as per IEC 60092-360, SHF2 or SHF2 Oil & Mud
Standard Applied
- Design guideline : IEC 60092-376 & NEK 606-2016
- Material
Insulation : EPR, IEC 60092-360
Sheath : SHF2, IEC 60092-360
- Flame retardant : IEC 60332-3-22, Cat.A
- Fire resistance : IEC 60331-1,2
- Halogen free properties : IEC 60754-1,2 & IEC 60684-2
- Low smoke properties : IEC 61034-1,2
- Sunlight resistance : UL 1581
- Cold properties (option) : CSA C22.2 No.03 (Bending : -40C, Impact : -35C)
- Oil/Mud resistance (option) : NEK 606-2016 (Category a, b, c, d)
Identification of color
- Insulation
- 1Pair : Black, Light Blue
- 2Pair and above : Numbering on Black & Light Blue insulation core
Note) Any other colors purchaser required
- Outer sheath : Grey (or Light blue for I.S. cable)
Note) Any other colors purchaser required
Type approval
- ABS, BV, DNV, LR
Marking
NEXANS KUKDONG S104 BFOU(C) 250V 7PRx1.5 SQMM IEC 60332-3 A IEC 60331 year length